Customization: | Available |
---|---|
Application: | Construction, Underground, Power Station |
Voltage: | Low and Medium Voltage Cable |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
NO.OF CORES | NOMINAL CROSS SECTIONALAREA mm² |
NOMINAL OVERALL DIAMETER mm |
NOMINAL WEIGHT kg/km |
1 | 50 | 29.3 | 782 |
1 | 95 | 32.4 | 1007 |
1 | 150 | 36 | 1278 |
1 | 185 | 36.9 | 1398 |
1 | 240 | 39.3 | 1626 |
1 | 400 | 44.2 | 2205 |
1 | 630 | 52.1 | 3208 |
NOMINAL CROSS SECTIONAL AREA mm² |
MAXIMUM CONDUCTOR DC RESISTANCE AT 20ºC Q/Km |
MAX. CONDUCTOR AC RESISTANCE AT OPERATING TEMP.AND 50HZ Q/Km |
MAXIMUM ELECTRICAL RESISTANCE OF AL FOIL SCREEN Q/Km |
CAPACITANCE μF/Km | CHARGING CURRENT A/Km |
DIELECTRIC LOSSES W/Km |
REACTANCE AT 50 HZ ohm/km |
cONDUCTOR S.C.CFOR 1 SEC KA |
SCREEN S.C.CFOR 1 SEC KA |
CURRENT RATING A | |
Laid in ground | Laid in free air | ||||||||||
50 95 |
0.641 | 0.822 | 1.551 | 0.177 | 0.666 | 31.97 | 0.141 | 4.7 | 1.71 | 180 | 197 |
0.32 | 0.411 | 1.344 | 0.217 0.264 | 0.82 | 39.36 | 0.127 | 8.9 | 1.91 | 265 | 298 | |
150 | 0.206 | 0.265 | 1.186 | 0.996 | 47.82 | 0.116 | 14.1 | 2.21 | 338 | 390 | |
185 | 0.164 | 0.211 | 1.045 | 0.276 | 1.04 | 49.92 | 0.113 | 17.3 | 2.21 | 387 | 449 |
240 | 0.125 | 0.161 | 1.08 | 0.307 | 1.157 | 55.51 | 0.109 | 22.5 | 2.41 | 444 | 534 |
400 | 0.0778 | 0.101 | 0.876 | 0.369 | 1.393 | 66.87 | 0.100 | 37.5 | 2.71 | 574 | 714 |
630 | 0.0469 | 0.062 | 0.749 | 0.47 | 1.773 | 85.10 | 0.094 | 59 | 3.32 | 755 | 966 |
NO.OF CORES | NOMINAL CROSS SECTIONALAREA mm² |
NOMINAL OVERALL DIAMETER mm |
NOMINAL WEIGHT kg/km |
1 | 50 | 34.3 | 1025 |
1 | 95 | 37.4 | 1272 |
1 | 150 | 41 | 1571 |
1 | 185 | 41.9 | 1701 |
1 | 240 | 44.3 | 1941 |
1 | 400 | 49.2 | 2561 |
1 | 630 | 57.1 | 3620 |
NOMINAL CROSS SECTIONAL AREA mm² |
MAXIMUM CONDUCTOR DC RESISTANCE AT 20ºC Q/Km |
MAXIMUM CONDUCTOR AC RESISTANCE AT OPERATING TEMP.AND 50HZ Q/Km |
MAXIMUM ELECTRICAL RESISTANCE OF AL FOIL SCREEN Q/Km |
CAPACITANCE μF/Km | CHARGING CURRENT A/Km |
DIELECTRIC LOSSES W/Km |
REACTANCE AT 50 HZ ohm/km |
cONDUCTOR S.C.CFOR 1 SEC KA |
SCREEN S.C.CFOR 1 SEC KA |
CURRENT RATING A | |
Laid in ground | Laid in free air | ||||||||||
50 95 |
0.641 | 0.822 | 1.26 | 0.138 | 0.78 | 56.14 | 0.151 | 4.7 | 2.01 | 180 | 202 |
0.32 | 0.411 | 1.045 | 0.167 | 0.943 | 67.89 | 0.136 | 8.9 | 2.21 | 266 | 302 | |
150 | 0.206 | 0.265 | 1.08 | 0.199 | 1.128 | 81.25 | 0.124 | 14.1 | 2.51 | 339 | 398 |
185 | 0.164 | 0.211 | 0.96 | 0.208 | 1.174 | 84.55 | 0.121 | 17.3 | 2.61 | 388 | 455 |
240 | 0.125 | 0.161 | 0.877 | 0.229 | 1.296 | 93.33 | 0.116 | 22.5 | 2.71 | 448 | 539 |
400 | 0.0778 | 0.101 | 0.775 | 0.273 | 1.543 | 111.11 | 0.107 | 37.5 | 3.11 | 579 | 719 |
630 | 0.0469 | 0.062 | 0.672 | 0.343 | 1.938 | 139.52 | 0.100 | 59 | 3.62 | 760 | 980 |